Conduit, Pipe & Tube Applications

Pipe Clamp Application - System Overview-02-01

1)  Pipe & Conduit Clamps


For RMC / GRC Conduit, Schedule 10, 40 & 80 Pipe

RMC & Pipe Clamp OPM Capacities 2

OPM-0295-13 (Page 5d.1)              P1100 Series Pipe Clamps



Notes:

* Schedule 40 or heavier pipe, or RMC/GRC only.

For EMT & IMCEMT & IMC Conduit Clamp OPM Capacities

OPM-0295-13 (Page 5d.2)               P1400 Series Conduit Clamps               P1100 Series Pipe Clamps

 

For Copper Tube (Types K, L, M)Copper Tube OPM Capacities

OPM-0295-13 (Page 5d.3)               P2600 UNICUSHION               P2000 Series O.D. Clamps               P1400 Series Conduit Clamps

 


2)  Trapeze Beam


Maximum Allowable Uniform Vertical Load (lbs)Trapeze Beam OPM Capacities

Notes:

1.  Values in this table apply only to Unistrut brand products. Unistrut channels are stamped with the name "UNISTRUT".

2.  Values in this table are valid with all solid, T, WT and HS pierced channels of the above channel profiles.

3.  * Load is limited by spot weld shear. Weld shear and tension are accounted for in the above listed capacities.

4.  Refer to OPM Page 4b.0 for the detailed calculation procedure.


3)  Brace Member


Maximum Horizontal FP Force (lbs) [ASD] at 45° from HorizontalBrace Member OPM Capacities

Notes:

1.  Values in this table apply only to Unistrut brand products. Unistrut channels are stamped with the name "UNISTRUT".

2.  Values in this table are valid with all solid, T, WT and HS pierced channels of the above channel profiles.

3.  Only the 45° capacities are shown above, but these brace members are valid for angles from 0° to 60° from horizontal. Refer to product or OPM pages for capacities at other angles.


4)  Brace Fitting


FP Load Capacity (lbs)

Brace Fitting OPM Capacities

Notes:

  1. Use with P3860 base.
  2. Use with LS 100 base.
  3. Use with LS 200 base.
  4. All angles above are from horizontal. All loads are based on use with a 1/2" or larger fastener and connected per one of the connection details outlined below.

5)  Connection Details

Connection Detail - Brace Bolted to Channel-01

Brace Bolted to Channel

(OPM Page 5a.1)

3" Min. End Distance

  • FP Transverse = 1,370 lbs
  • FP Longitudinal = 1,035 lbs (640 lbs opp.)
  • FP Vertical = 2,810 lbs
  • Connection Detail - Brace Bolted to Channel w Wolf Washer-01

    Brace Bolted to Channel

    (OPM Page 5a.2)

    Flush to End

  • FP Transverse = 2,375 lbs
  • FP Longitudinal = 935 lbs (640 lbs opp.)
  • FP Vertical = 2,605 lbs
  •  

    Connection Detail - Brace Around Rod to Channel-01

    Brace Around Rod to Channel

    (OPM Page 5a.3)

    3" Min. End Distance

  • FP Transverse = 1,370 lbs
  • FP Longitudinal = 1,035 lbs (640 lbs opp.)
  • FP Vertical = 2,810 lbs
  •  

    Connection Detail - Brace Around Rod to Channel 2-01

    Brace Around Rod to Channel

    (OPM Page 5a.4)

    Flush to End

  • FP Transverse = 2,375 lbs
  • FP Longitudinal = 935 lbs (640 lbs opp.)
  • FP Vertical = 2,605 lbs
  •  

    Connection Detail - Brace Around Rod thru Channel-01

    Brace Around Rod Thru Channel

    (OPM Page 5a.5)

    1-1/2" Min. End Distance

  • FP Transverse = 1,565 lbs
  • FP Longitudinal = 935 lbs (640 lbs opp.)
  • FP Vertical = 2,068 lbs
  •  

    Connection Detail - Rod thru Channel-01

    Rod Thru Channel

    (OPM Page 5a.6)

    Flush to End

    • FP Vertical = 2,068 lbs
    Connection Detail - Rod to Channel Standard-01

    Rod to Channel

    (OPM Page 5a.7)

    3" Min. End Distance

    • FP Vertical = 2,065 lbs
    Connection Detail - Rod to Channel w Wolf Washer-01

    Rod to Channel

    (OPM Page 5a.7)

    Flush to End

    • FP Vertical = 2,065 lbs

    6)  Rod Stiffeners

    Rod Stiffener Detail-01
    Rod Stiffener Charts-01