P5001 - 1-5/8" x 6 1/2", 12 Gage, Back-to-Back, Solid
Unistrut's P5001 (back-to-back solid) channel is our 12 gauge channel that is commonly used for trapeze supports, seismic bracing, ceiling grids, pipe, conduit, duct and cable tray supports, racks, and other general framing. For application examples, refer to our Application Showcase.
Product dimensions are 1 5/8" wide x 6 1/2" tall x 12 ga. thick, solid. Punched holes are also available for ease of installation. The advantage of a back-to-back channel is the versatile connection points and superior load capabilities.
Our P5001 is available in the following finishes: Pre-Galvanized (PG), Unistrut Defender (DF), Hot-Dip Galvanized (HG), Plain (PL), Green (GR), Zinc Dichromate (ZD), Stainless Steel (SS or ST) and Aluminum (EA).
Part No. | Length (ft) | Finish | Product Weight / Ft (lbs/ft) |
---|---|---|---|
P5001 | 20 | PG | 6.1 |
P5001 | 10 | PG | 6.1 |
P5001 | 10 | HG | 6.466 |
P5001 | 20 | HG | 6.466 |
P5001 | 20 | GR | 6.1 |
P5001 | 10 | GR | 6.1 |
P5001 | 10 | PL | 6.1 |
P5001 | 20 | PL | 6.1 |
Beam Loading
Beam Loading - P5001 | ||||||
---|---|---|---|---|---|---|
Span
(in) |
Max Allow. Uniform Load
(lbs) |
Deflection at Uniform Load
(in) |
Uniform Loading at Deflection | Lateral Bracing Reduction Factor | ||
Span/180
(lbs) |
Span/240
(lbs) |
Span/360
(lbs) |
||||
24 | * 6,890 | 0.01 | * 6,890 | * 6,890 | * 6,890 | 1.00 |
36 | * 6,890 | 0.02 | * 6,890 | * 6,890 | * 6,890 | 1.00 |
48 | * 6,890 | 0.05 | * 6,890 | * 6,890 | * 6,890 | 0.97 |
60 | 6,420 | 0.10 | 6,420 | 6,420 | 6,420 | 0.90 |
72 | 5,350 | 0.14 | 5,350 | 5,350 | 5,350 | 0.83 |
84 | 4,590 | 0.19 | 4,590 | 4,590 | 4,590 | 0.76 |
96 | 4,020 | 0.25 | 4,020 | 4,020 | 4,020 | 0.68 |
108 | 3,570 | 0.32 | 3,570 | 3,570 | 3,360 | 0.61 |
120 | 3,210 | 0.39 | 3,210 | 3,210 | 2,720 | 0.54 |
144 | 2,680 | 0.57 | 2,680 | 2,680 | 1,890 | 0.43 |
168 | 2,290 | 0.77 | 2,290 | 2,080 | 1,390 | 0.35 |
192 | 2,010 | 1.01 | 2,010 | 1,590 | 1,060 | 0.30 |
216 | 1,780 | 1.27 | 1,680 | 1,260 | 840 | 0.27 |
240 | 1,610 | 1.58 | 1,360 | 1,020 | 680 | 0.24 |
Note | Bearing load may govern capacity. | |||||
Note | *Load limited by weld shear |
Column Loading
Column Loading - P5001 | |||||
---|---|---|---|---|---|
Unbraced
Height (in) |
Allowable
Load at Slot Face (lbs) |
Max Column Load Applied at C.G. | |||
K=0.65 (lbs) | K=0.80 (lbs) | K=1.0 (lbs) | K=1.2 (lbs) | ||
24 | 10,670 | 39,230 | 38,030 | 36,210 | 34,240 |
36 | 10,350 | 36,450 | 34,240 | 31,200 | 28,260 |
48 | 9,940 | 33,220 | 30,200 | 26,430 | 23,190 |
60 | 9,290 | 29,950 | 26,430 | 22,470 | 19,380 |
72 | 8,560 | 26,880 | 23,190 | 19,380 | 16,450 |
84 | 7,860 | 24,140 | 20,520 | 17,040 | 12,090 |
96 | 7,220 | 21,790 | 18,370 | 13,330 | 9,250 |
108 | 6,600 | 19,790 | 16,450 | 10,530 | 7,310 |
120 | 5,760 | 18,130 | 13,330 | 8,530 | KL/r>200 |
144 | 4,390 | 14,020 | 9,250 | KL/r>200 | KL/r>200 |
168 | 3,420 | 10,300 | 6,800 | KL/r>200 | KL/r>200 |
Elements of Section
Elements of Section - P5001 | ||
---|---|---|
Area of Section | 1.793 in2 (11.6 cm2) | |
Axis 1-1 | Axix 2-2 | |
Moment of Inertia (I) | 6.227 in4 (259.2 cm4) | 0.866 in4 (36 cm4) |
Section Modulus (S) | 1.916 in3 (31.4 cm3) | 1.066 in3 (17.5 cm3) |
Radius of Gyration (r) | 1.864 in (4.7 cm) | 0.695 in (1.8 cm) |
General Specifications
Standard Lengths:
- 10 feet: 10' or 10’ 1/8” (3.05m) ± 1/8" (3 mm)
- 20 feet: 20' or 20’ 3/8” (6.11m) ± 1/8" (3 mm)
Special Lengths:
- Available with a tolerance of ±1/8" (3 mm). Request quote.
Curved Channel:
- Many Unistrut channel sections can be supplied with a curve. Click here for our ordering form, specifications, and instructions.
Load Data:
- All beam and column load data pertains to carbon steel and stainless steel channels.
- Load tables apply only to UNISTRUT brand channel. Look for "UNISTRUT" on the product.
- Load tables and charts are constructed to be in accordance with the SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS 2007 EDITION published by the AMERICAN IRON AND STEEL INSTITUTE USING ASD METHOD.
- Loads are based on 33 ksi steel cold formed to 42 ksi.
- Safety Factor to Yield Strength is 1.67 for Beam Loads and 1.80 for Column Loads.
- Beam loads are based on a simple beam and are given as a total uniform load (W) in pounds. For proper calculation procedures, refer to our Beam Load Calculation Guide.
- For bearing loads, reference our bearing loads page.
Welds:
- Welded channels are spot welded 2" (51 mm) or 3" (76 mm) on-center.
Materials & Finishes
Materials & Finishes - Standard:
- Pregalvanized (PG): Conforms to ASTM A653 SS GR 33, G90.
- Unistrut Defender (DF): Conforms to ASTM A1046 SS GR 33
- Hot Dip Galvanized (HG): Steel conforms to ASTM A1011 SS GR 33, Finish conforms to ASTM A123
- Perma-Green (GR): Steel conforms to ASTM A1011 SS GR 33, E-Coat finish
- Perma-Gold (ZD): Steel conforms to ASTM A1011 SS GR 33, Finish conforms to ASTM B633, Type II SC3
- Plain (PL): Conforms to ASTM A1011 SS GR 33
- Stainless Steel, Type 304 (SS): ASTM A240, Type 304 *
- Stainless Steel, Type 316 (ST): ASTM A240, Type 316 *
- Aluminum (EA): ASTM B221, Type 6063-T6 (Extruded) *
* These materials have different physical properties and performance characteristics. Please contact us for design support.